Voltage drop

Resistive drop along a copper or aluminum conductor.

Circuit
Material

Greater than 0, up to 1,000,000.

Greater than 0, up to 1,000,000.

Greater than 0, up to 1,000,000.

Greater than 0, up to 1,000,000.

Length is one way. Single-phase already counts the return path. Copper is 0.0168 and aluminum is 0.0265 ohm square millimetre per metre, at 20°C.

Enter current, length, cross-section, and source voltage.

How voltage drop works

The voltage drop is the voltage lost along a conductor. One-way resistance is resistivity times length, divided by cross-section. Single-phase multiplies by 2 because the current travels out and back. Three-phase multiplies by the square root of 3.

Length is in metres and cross-section is in square millimetres. Copper is 0.0168 ohm square millimetre per metre and aluminum is 0.0265, both at 20°C. Each entered number is greater than 0 and at most 1,000,000. A blank field, zero, or a negative number has no result.

How to use this voltage drop calculator

  1. Choose single-phase or three-phase, and copper or aluminum.
  2. Enter current, one-way length, cross-section, and source voltage. Each is greater than 0 and at most 1,000,000.
  3. Read the drop. The rows below are the percent of the source voltage and the resistance of one conductor.

Formula

For single-phase, and for a direct-current pair of wires, the drop is twice the one-way resistance times the current.

Single-phase voltage drop
Vd=2⁢ρ⁢L⁢IS

Three-phase replaces 2 with the square root of 3. One-way resistance is rho L divided by S. Percent is the drop divided by the source voltage, times 100. The source voltage does not change the drop.

Where the formula comes from

The loss along a conductor is the relation on the Wikipedia page that defines voltage drop. The resistance of a uniform conductor is the relation on the Wikipedia page that defines electrical resistivity and conductivity.

Worked examples

Example: single-phase copper, 10 A, 50 m, 2.5 mm², 230 V

One-way resistance is 0.0168 × 50 ÷ 2.5 = 0.336 ohm. The drop is 2 × 10 × 0.336 = 6.72. Percent is 6.72 ÷ 230 × 100 = 2.92173913043.

Example: three-phase copper, the same wire, 400 V

Resistance stays 0.336 ohm. The drop uses the square root of 3 instead of 2, so it is 5.81969071343. Percent of 400 is 1.45492267836.

Example: single-phase aluminum, 10 A, 50 m, 2.5 mm², 230 V

One-way resistance is 0.0265 × 50 ÷ 2.5 = 0.53 ohm. The drop is 2 × 10 × 0.53 = 10.6. Percent is 4.60869565217.

Example: single-phase copper, 5 A, 10 m, 1 mm², 12 V

One-way resistance is 0.0168 × 10 ÷ 1 = 0.168 ohm. The drop is 2 × 5 × 0.168 = 1.68. Percent of 12 is 14.

Things to keep in mind

Enter the one-way length. Single-phase already includes the return path. A near integer is shown as that integer. Other results keep 12 significant digits. This page uses resistance only: no temperature change, no reactance, and no power factor. It does not read a resistor color code.

Voltage drop calculator FAQ

Which fields are required?

Current, one-way length, cross-section, and source voltage. Each is greater than 0 and at most 1,000,000. The starting choices are single-phase and copper.

Why does single-phase use 2?

The current goes out and comes back, so both conductors drop voltage. Direct current with two wires uses the same factor. Three-phase uses the square root of 3. Do not enter the round-trip length yourself.

Which resistivity is used?

Copper is 0.0168 ohm square millimetre per metre and aluminum is 0.0265, both at 20°C. The temperature does not change.

What are the two rows?

Percent is the drop divided by the source voltage, times 100. Resistance is one conductor, resistivity times length divided by cross-section. Changing the source voltage changes the percent and leaves the drop the same.

Why is there no result?

A blank field, zero, or a negative number has no result. The same is true above 1,000,000.

Does this voltage drop calculator store my numbers?

A completed result can be saved in this browser’s local history, including the circuit, the material, and the current, length, cross-section, and source voltage you entered. It stays on your device and is not sent to our servers or to analytics. Clear it with the history Clear action or by clearing site data.